71
5.4.8 System control parameters
The
“1 SysPara” menu has 6 submenus, including ”1 GridVProtect”, ”2
GridFProtect”, ”3 ON/OFF”, ”4 PowerContr”, ”5 LVRTSet” and ”6
OtherProtect”.
(1)
”1 GridVProtect” and ”2 GridFProtect” menus: Set up the parameters of
grid voltage, frequency protection and recovery, etc, as shown in Table 5-3:
Table 5-3 Parameters of grid voltage and frequency
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridV.Max1(V)
Threshold value of Level 1
Max. grid voltage
{200.0, 440.0, 533.0}
VMaxTripT1(S)
Threshold value of Level 1
Max. grid trip voltage
{0, 600.00, 600.00}
GridV.Min1(V)
Threshold value of Level 1
Min. grid voltage
{0, 360.0, 480.0}
VMinTripT1(S
)
Threshold value of Level 1
Min. grid trip voltage
{0, 600.00, 600.00}
GridV.Max2(V)
Threshold value of Level 2
Max. grid voltage
{200.0, 460.0, 624.0}
VMaxTripT2(S)
Threshold value of Level 2
Max. grid trip voltage
{0, 0.10, 600.00}
GridV.Min2(V)
Threshold value of Level 2
Min. grid voltage
{0, 320.0, 480.0}
VMinTripT2(S)
Threshold value of Level 2
Min. grid trip voltage
{0, 0.10, 600.00}
GridVmaxRecT(V)
Recovery threshold value {200.0, 437.4, 533.0}
permitted.
Содержание CPS SCA20KTL-DO
Страница 1: ...CPS SCA Series Grid tied PV Inverter CPS SCA20 25KTL DO Installation and Operation Manual Ver 1 0 ...
Страница 18: ...14 3 2 Mechanical installation 1 Dimensions Figure 3 2 Dimensions of CPS SCA20 25KTL DO series inverter ...
Страница 56: ...52 Figure 3 48 The ZigBee cable connection a b c d e ...
Страница 97: ...93 1 5 2 4 3 ...
Страница 98: ...94 Figure 7 1 Replace cooling fans 50 60mm mm 50 60mm mm 6 ...