79
Table 5-8 Protection parameters of LVRT control
Parameter name
Description
Setup range (lower limit, default
& upper limit)
LVRTProtect
LVRT
protection
enable/disable
{Ban, Ban,Enable2}
LVRTVoltLimit(%)
LVRT voltage limit {70.0,80.0,90.0}
LVRTPosCurrK
LVRT
positive
current K
{0,1.5,100}
LVRTNegCurrK
LVRT
negative
current K
{0,2.0,100}
(5)
”6 OtherProtect” menu: set up the threshold value of leakage current and
output DC component protection:
Table 5-9 Protection parameters of leakage current and output DC component
Parameter name
Description
Setup range (lower limit, default
& upper limit)
LeakCurMax(mA)
Leakage
current
Max. limit
{0, 250, 300}
IdcMax(mA)
DC
component
current Max. limit
{0, 140, 1000}
(CPS SCA20KTL)
{0, 180, 1000}
(CPS SCA25KTL)