77
QuCurveU2i(V)
(330.0
,
358.5
,
367.0)
See Figure 5-18
QuCurveQ2i(%
)
(-100.0%,
-50.1%
,
100.0%)
See Figure 5-18
QuCurvTripP
(
%
)
(5.0%
,
20.0%
,
100.0%)
Qu
curve
trip
power
QuCurveReP
(
%
)
(5.0%
,
5.0%
,
100.0%)
Qu
curve
revocation power
“FreqDeratCtrl” menu: Set up the parameters of over-frequency active
power deraring.
Table 5-7 Protection parameters of active power derating (VDE-4105)
Parameter name
Description
Setup range (lower limit,
default & upper limit)
FreqDeratSet
Over-frequency
derating
setting
{Ban,Enable1,Enable2}
GridOFDerat1(Hz) Derating frequency 1
{50.00,50.20,65.00}
DeratRatio(%/Hz)
Derating ratio
{0,40.0,100.0}
DePowStep(KW/S) Derating power recovery step
{0.01,0.03,2.00}
(CPS SCA20KTL)
{0.01,0.04,2.00}
(CPS SCA25KTL)
GridOFDerat3(Hz) Derating recovery frequency3 {49.00,50.00,61.00}
GridOFDeT3(S)
Derating frequency recovery
time
{0,300.00,600.00}
When the grid standard is VDE-4105, the setting range of trip frequency
of over-frequency derating is (50.00Hz
,
51.50Hz), and the default value is
50.20Hz. The range of over-frequency derating slope is (0
,
100%), and the
default value is 40.0%.
Содержание CPS SCA20KTL-DO
Страница 1: ...CPS SCA Series Grid tied PV Inverter CPS SCA20 25KTL DO Installation and Operation Manual Ver 1 0 ...
Страница 18: ...14 3 2 Mechanical installation 1 Dimensions Figure 3 2 Dimensions of CPS SCA20 25KTL DO series inverter ...
Страница 56: ...52 Figure 3 48 The ZigBee cable connection a b c d e ...
Страница 97: ...93 1 5 2 4 3 ...
Страница 98: ...94 Figure 7 1 Replace cooling fans 50 60mm mm 50 60mm mm 6 ...