67
5.4.6 AutoTest
The “6 Autotest” appears ONLY when users select the “CEI 0-21” grid
standard. Users can do the Class I and Class II protection tests to the grid
voltage and frequency by Class I and Class II protection tests.
Select “6 Autotest” and press
ENT
to go to the 8 submenus, including
“1
VMaxTest1”
,
“2 VMinTest1”, “3 FMaxTest1”
,
“4 FMinTest1”
,
“5 VMaxTest2”, “6
VMinTest2”, “7 FMaxTest2”
and
“8 FMinTest2”.
Take the “1 VMaxTest1” for example. When you select this submenu and
press
ENT
, “VMaxTest1 Start?” will appear on the LCD screen for your
confirmation. You can press
ESC
to cancel the test. If press
ENT
again, you
will see “Testing...” on the LCD screen. When the test is complete, the test
result will be reported on the screen. Then press
ESC
to go back to the 8
submenus for other tests with the same test steps.
INSTRUCTION:
The Autotest is only needed for CEI 0-21 grid standard.
INSTRUCTION:
The Autotest function is ONLY available when the inverter is in
normal operation mode.