70
(3)
“3 Recover” menu: The manufacturer’s parameter default value can be
restored when the inverter is not in operation mode. Otherwise
“Fault
Operated
” will be reminded.
(4)
“4 ClrErrRecd” menu: History information of the failures can be wiped
clear after confirmation
(5) “5 Stdset” menu: The grid standard can only be changed when the inverter
is turned off by LCD shut down. The change is ineffective under normal operation
mode. Please refer to
“6.2 Shut down” after the inverter stops working, and choose
the grid standard as per the local requirement of the electricity supply company.
INSTRUCTION:
This function is effective only when the fault “IntFault0010~0150” in
the troubleshooting table occurs. The inverter may restore to normal
operation automatically if alarm or protection faults occur. This
function will not respond when the inverter is in operation mode and a
“FaultOperated” alarm interface will be indicated.
NOTICE:
Please don
’
t change the grid standard when the inverter is in
normal operation mode, or the change is invalid. Please refer to the
“
6.2 Manual shutdown
”
to turn off the inverter.
INSTRUCTION:
CPS SCA20/25KTL-DO series PV inverter supports 7 grid
standards. Please check with your local electricity supply company
before selecting the grid standard. If the inverter is operated with a
wrong grid standard, the electricity supply company may cancel the
operation license.
Putting the inverter into operation before the overall system complies
with the national rules and safety regulation of the application is not
Содержание CPS SCA20KTL-DO
Страница 1: ...CPS SCA Series Grid tied PV Inverter CPS SCA20 25KTL DO Installation and Operation Manual Ver 1 0 ...
Страница 18: ...14 3 2 Mechanical installation 1 Dimensions Figure 3 2 Dimensions of CPS SCA20 25KTL DO series inverter ...
Страница 56: ...52 Figure 3 48 The ZigBee cable connection a b c d e ...
Страница 97: ...93 1 5 2 4 3 ...
Страница 98: ...94 Figure 7 1 Replace cooling fans 50 60mm mm 50 60mm mm 6 ...