76
The Table 5-6 lists the parameters of QReactSet, PF Set, PF(P) Curve
and Q(U) Curve modes. Press
ENT
to start up the modes after the parameters
are set up.
Figure 5-6 Parameters of reactive power control
Mode
Parameter
Name
Setup range (lower limit,
default & upper limit)
Description
Q
ReactiveComp(
%)
(-100.0%
,
0.0%
,
100.0%)
PF
PowerFactor
(-1.000
,
1.000
,
1.000)
PF(P)
PFCurveP1(%)
(0
,
50%
,
100%)
See Figure 5-17
PFCurvePF1
(-1.000
,
1.000
,
1.000)
See Figure 5-17
PFCurveP2(%)
(0
,
100%
,
100%)
See Figure 5-17
PFCurvePF2
(-1.000
,
-0.900
,
1.000)
See Figure 5-17
PFCurvTripV(V
)
(358.5
,
398.3
,
438.2)
PF
curve
trip
voltage
PFCurveReV(V
)
(0
,
358.5
,
438.2)
PF
curve
revocation
voltage
Q(U)
QuCurveU1(V)
(430.2
,
430.2
,
440.0)
See Figure 5-18
QuCurveQ1(%)
(-100.0%
,
0.0%
,
100.0%) See Figure 5-18
QuCurveU2(V)
(430.0
,
438.2
,
440.0)
See Figure 5-18
QuCurveQ2(%)
(-100.0%
,
50.0%
,
100.0%)
See Figure 5-18
QuCurveU1i(V)
(355.0
,
366.4
,
370.0)
See Figure 5-18
QuCurveQ1i(%
)
(-100.0%
,
0.0%
,
100.0%) See Figure 5-18
Содержание CPS SCA20KTL-DO
Страница 1: ...CPS SCA Series Grid tied PV Inverter CPS SCA20 25KTL DO Installation and Operation Manual Ver 1 0 ...
Страница 18: ...14 3 2 Mechanical installation 1 Dimensions Figure 3 2 Dimensions of CPS SCA20 25KTL DO series inverter ...
Страница 56: ...52 Figure 3 48 The ZigBee cable connection a b c d e ...
Страница 97: ...93 1 5 2 4 3 ...
Страница 98: ...94 Figure 7 1 Replace cooling fans 50 60mm mm 50 60mm mm 6 ...