26
Table 3-3 Cables specifications
Position
Cable
Max.
cable
length (m)
DC input (
﹢
/
﹣
)
2.5~4.0mm
2
PV cable
32
(2.5mm
2
)
AC
output
(L1/L2/L3/N/PE)
1) L1/L2/L3/N/PE:
5X6~16mm
2
cable,
outer diameter:21~26mm.
Recommend
ed cable for
L1/L2/L3/N/P
E:5X10mm
2
H07RN-F
32
(
10mm
2
)
2) L1/L2/L3/N: 4X6~16mm
2
cable,
outer diameter:21~26mm.
PE: 1X6~10mm
2
cable for
external grounding point
Recommend
ed cable for
L1/L2/L3/N:
4X10mm
2
H07RN-F
Recommend
ed cable for
PE:
1X10mm
2
Dry coantact
3x0.2~0.75mm
2
communication cable with
outer diameter of 4.5~6mm
RS485
communication
UTP
CAT-5e
or
3x0.2~0.75mm
2
communication cable with outer diameter of
4.5~6mm
1200
Ethernet
communication
UTP CAT-5e communication cable with
outer diameter of 4.5~6mm
100
Zigbee
No need for external cable connection
/