7
Long service life:
Uses thin-film capacitors
to extend inverter’s service life
2 MPPTs:
Support independent and parallel modes of PV connection
High protection degree:
IP65 protection degree meets the needs of both
indoor and outdoor use; Embedded DC switch makes field maintenance
more flexible and safer
2.3 Product protection functions
Polarity reverse protection of DC input
Short circuit protection
DC input insulation against ground monitoring
AC output voltage and frequency monitoring
Leakage current against ground monitoring
Monitoring of DC injection from AC output
Anti-islanding protection
Input and output over-voltage protection
Input over-current protection
Environmental temperature monitoring
Module temperature monitoring
2.4 Circuit structure design
The basic schematic diagram of CPS SCA20/25KTL-DO series inverter is
shown in Figure 2-2.
The input of PV modules passes through surge protection circuitry, DC
EMI wave filter, and the front-end boost circuitry to achieve maximum power
tracking and boost up voltages. The output of the inverter converts the DC
voltage to 3-phase AC voltage. The high frequency AC components are
removed with a wave filter. Then the 3-phase AC voltage is passed through
two-stage relays and EMI wave filter to produce high quality AC power.
Содержание CPS SCA20KTL-DO
Страница 1: ...CPS SCA Series Grid tied PV Inverter CPS SCA20 25KTL DO Installation and Operation Manual Ver 1 0 ...
Страница 18: ...14 3 2 Mechanical installation 1 Dimensions Figure 3 2 Dimensions of CPS SCA20 25KTL DO series inverter ...
Страница 56: ...52 Figure 3 48 The ZigBee cable connection a b c d e ...
Страница 97: ...93 1 5 2 4 3 ...
Страница 98: ...94 Figure 7 1 Replace cooling fans 50 60mm mm 50 60mm mm 6 ...