32
Figure 3-23 Assemble male connector on DC positive cable
Figure 3-24 Assemble female connector on DC negative cable
Remark: Confirm the following points before connecting the DC cables to
the inverter:
1. Make sure the PE cable is well connected. Please refer to 3.3.2 for
detailed information of ground connection.
2. Turn off the DC switch.
(f) Plug the assembled DC cable connectors with the positive and
negative connectors on the inverter side respectively, as shown in
Figure 3-25:
Figure 3-25 Plug DC cable connectors
If the input connector needs to be unlocked, put the unlock tool for DC
connector into the slot on the connector, and unlock the connector by pressing
down the unlock tool, as shown in Figure 3-26 & Figure 3-27: