N.O. N.C. COM
Figure 3-35 Dry contact communication port
The voltage and current rating of the dry contact shown in the following
table must not be exceeded in any case.
Table 3-10 Rating of dry contact
Voltage
Current
AC
Maximum 277 V
Maximum 3 A
DC
Maximum 30 V
Maximum 1 A
Different modes of dry contact output can be accessed by connecting
different pins of the P205 connector, as shown in following table.
Table 3-11 Working modes of dry contact
Dry contact communication
port
Status in fault
condition
Status without fault
condition
P205: N.O.
— COM
Closed
Open
P205: N.C.
— COM
Open
Closed
Connection Plan:
You can connect a LED or other loads to indicate the operational status of
the inverter, as shown in the following figure: