4) Installation space requirement (see Figure 3-4):
The distances between the inverters or the surrounding objects should
meet the following conditions:
≥300mm
(11.8in.)
≥500mm
(19.7in.)
≥1000mm
(39.4in.)
≥600mm
(23.6in.)
Figure 3-4 Inverter mounting dimensions
5) Mount the inverter onto the bracket
(1) Mark the 8 holes on the bearing surface for mounting the bracket as
shown in Figure 3-5;
NOTICE:
The spacing between two inverters
in parallel should be ≥1000mm
(39.4 inches). Ensure that the air space around the inverter is well
ventilated.