Parameters
Display and measuring parameters
68
Controller BUS 6 T
5.94017.06
Baumüller Nürnberg GmbH
amplifier warning temperature
If the amplifier temperature exceeds the amplifier warning temperature, the drive sets the
bit "amplifier warning temperature" in Class 2 Diagnostics (see ID no. 12).
NOTE
Exceeding the temperature does not cause pulse or controller inhibit.
amplifier shutdown temperature
If the amplifier temperature exceeds the amplifier shutdown temperature, the drive sets the
bit "amplifier shutdown temperature" in Class 1 Diagnostics (see ID no. 11).
NOTE
Exceeding the temperature causes controller inhibit.
motor warning temperature
If the motor temperature exceeds the motor warning temperature, the drive sets the bit
"excess motor temperature warning" in Class 2 Diagnostics (see ID no. 12). With DS motors
this function is not evaluated.
NOTE
Exceeding the temperature does not cause pulse or controller inhibit.
motor shutdown temperature
If the motor temperature exceeds the motor shutdown temperature, the drive sets the bit
"excess motor temperature shutdown" in Class 1 Diagnostics (see ID no. 11).
NOTE
Exceeding the temperature causes controller inhibit.
Содержание BUS 6-T Series
Страница 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 16: ...Type code Technical data 10 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 26: ...Installation Terminal Diagram 20 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 5 4 Terminal diagram I ...
Страница 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 45: ...Initial commissioning Commissioning Controller BUS 6 T 39 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 46: ...Commissioning Initial commissioning 40 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 47: ...Initial commissioning Commissioning Controller BUS 6 T 41 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 49: ...Main spindle area Commissioning Controller BUS 6 T 43 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 56: ...Parameters Basic settings 50 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 7 2 Basic settings ...
Страница 79: ...Parameter set 0 Parameters Controller BUS 6 T 73 Baumüller Nürnberg GmbH 5 94017 06 7 4 Parameter set 0 ...
Страница 85: ...Parameter set 0 Parameters Controller BUS 6 T 79 Baumüller Nürnberg GmbH 5 94017 06 7 4 3 Speed controller ...
Страница 106: ...Maintenance Status messages 100 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 8 2 Status messages ...