Basic settings
Parameters
Controller BUS 6 T
59
Baumüller Nürnberg GmbH
5.94017.06
set magnetising current value (I
α
αα
α
N
)
The magnetising current value is always 0 by synchronous motors.
magnetising current limitation (I
α
αα
α
G
)
The maximum value of the magnetising current is entered via these parameters.
Sychronous motors:
typical value 5 A ... 20 A
Asynchronous motors:
1.2 x set magnetising current value (ID no. 32814)
set active current value (I
ββββ
N
)
I
I
I
N
N
N
β
α
=
−
2
2
active current limitation (I
ββββ
G
)
The active current limitation is entered via this parameter.
Asynchronous motors:
1.2 x set active current value (ID no. 32804)
time constant of actual torque value
This parameter specifies the time constant of the actual torque value.
Typical value 1 ms ... 3 ms.
set apparent current value(I
N
)
apparent current limitation(I
NG
)
This parameter displays the set value and the limitation of the apparent current.
torque controller gain
torque controller integral-action time
These parameters indicate the torque controller's gain and its integral-action time.
flux controller gain
flux controller integral-action time
These parameters specify the flux controller's gain and its integral-action time.
Содержание BUS 6-T Series
Страница 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 16: ...Type code Technical data 10 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 26: ...Installation Terminal Diagram 20 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 5 4 Terminal diagram I ...
Страница 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 45: ...Initial commissioning Commissioning Controller BUS 6 T 39 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 46: ...Commissioning Initial commissioning 40 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 47: ...Initial commissioning Commissioning Controller BUS 6 T 41 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 49: ...Main spindle area Commissioning Controller BUS 6 T 43 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 56: ...Parameters Basic settings 50 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 7 2 Basic settings ...
Страница 79: ...Parameter set 0 Parameters Controller BUS 6 T 73 Baumüller Nürnberg GmbH 5 94017 06 7 4 Parameter set 0 ...
Страница 85: ...Parameter set 0 Parameters Controller BUS 6 T 79 Baumüller Nürnberg GmbH 5 94017 06 7 4 3 Speed controller ...
Страница 106: ...Maintenance Status messages 100 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 8 2 Status messages ...