Display and measuring parameters
Parameters
Controller BUS 6 T
67
Baumüller Nürnberg GmbH
5.94017.06
7.3.4 Temperature monitoring
Parameter overview
ID no.
Name
Range
min. ... max.
Unit
Standard
value
Display
only
Temperature monitoring
32782
actual circuitry housing temperature
value
0.0 ... 100.0
°C
32783
actual amplifier temperature value
-100.0 ... 100.0
°C
32784
actual motor temperature value
0.0 ... 160.0
°C
202
cooling-error warning temperature
0 ... 100.0
°C
75
205
cooling-error shutdown temperature
0 ... 100.0
°C
85
200
amplifier warning temperature
0 ... 100.0
°C
75
203
amplifier shutdown temperature
0 ... 100.0
°C
95
201
motor warning temperature
0 ... 150.0
°C
130
204
motor shutdown temperature
0 ... 160.0
°C
150
Parameter description
actaul circuitry housing temperature value
This parameter displays the temperature in the circuitry housing.
actual amplifier temperature value
This parameter displays the power unit temperature.
actual motor temperature value
Display of motor temperature.
cooling-error warning temperature
If the temperature inside the circuitry housing exceeds the cooling-error warning
temperature, the drive sets the bit "cooling-error warning temperature" in Class 2
Diagnostics (see ID no. 12).
NOTE
Exceeding the temperature does not cause pulse or controller inhibit.
cooling-error shutdown temperature
If the temperature inside the circuitry housing exceeds the cooling-error shutdown
temperature, the drive sets the bit "cooling-error shutdown temperature" in Class 1
Diagnostics (see ID no. 11).
NOTE
Exceeding the temperature causes controller inhibit.
Содержание BUS 6-T Series
Страница 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 16: ...Type code Technical data 10 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 26: ...Installation Terminal Diagram 20 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 5 4 Terminal diagram I ...
Страница 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 45: ...Initial commissioning Commissioning Controller BUS 6 T 39 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 46: ...Commissioning Initial commissioning 40 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 47: ...Initial commissioning Commissioning Controller BUS 6 T 41 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 49: ...Main spindle area Commissioning Controller BUS 6 T 43 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 56: ...Parameters Basic settings 50 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 7 2 Basic settings ...
Страница 79: ...Parameter set 0 Parameters Controller BUS 6 T 73 Baumüller Nürnberg GmbH 5 94017 06 7 4 Parameter set 0 ...
Страница 85: ...Parameter set 0 Parameters Controller BUS 6 T 79 Baumüller Nürnberg GmbH 5 94017 06 7 4 3 Speed controller ...
Страница 106: ...Maintenance Status messages 100 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 8 2 Status messages ...