Leistungsteilkennung
Inbetriebnahme
Controller BUS 6 T
37
Baumüller Nürnberg GmbH
5.94017.06
6.1 Identification power unit
SV 03.06H (SM) and 83.01H (AM)
•
EEPROM not yet programmed or „Motor data acknowledged“ (ID no. 32917) = 0,
but type of power unit correctly recognized.
Consequence:
The motor parameter are initialized with the data from boot-EPROM and because of the
successfully recognition of the power unit´s type the parameter of the power unit are correctly
initialized.
Error message:
-
Software error BUS (ID no. 32908)
wrong type of motor (bit no. 10)
NOTE
This error can´t be deleted!
Motor parameter corresponding to the motor type must be inizialized and with the
command „motor data acknowledged“ (ID no. 32917) = 1 confirmed. The new data
has to be stored with the „command store“ (ID no. 32841).
•
Change of a already programmed controller to another type of power unit.
Consequence:
If the new power unit type is recognized correctly, all data except of:
-
Nominal current amplifier
ID no. 112
-
Maximum current amplifier
ID no. 110
-
Amplifier warning temperature
ID no. 200
-
Amplifier shut down temperature
ID no. 203
-
Maximum intermediate circuit voltage ID no. 32831
are read from the EEPROM (in software versions before, all data was replaced by boot data).
Error message:
-
Error software BUS (ID no. 32908)
wrong type of power unit (bit no. 11)
NOTE
Error can be deleted with „reset“!
If the new data isn´t stored in the EEPROM this error appears at every new switch on.
•
Power unit type isn´t recognizes at all.
Error message:
-
Error software BUS (ID no. 32908)
wrong type of power unit (bit no. 11)
power unit type not recognized (bit no. 2)
-
Error hardware BUS (ID no. 32907) Error in recognizing power unit type (bit no. 9)
NOTE
This errors cann´t be deleted!
Содержание BUS 6-T Series
Страница 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 16: ...Type code Technical data 10 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 26: ...Installation Terminal Diagram 20 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 5 4 Terminal diagram I ...
Страница 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 45: ...Initial commissioning Commissioning Controller BUS 6 T 39 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 46: ...Commissioning Initial commissioning 40 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 47: ...Initial commissioning Commissioning Controller BUS 6 T 41 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 49: ...Main spindle area Commissioning Controller BUS 6 T 43 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 56: ...Parameters Basic settings 50 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 7 2 Basic settings ...
Страница 79: ...Parameter set 0 Parameters Controller BUS 6 T 73 Baumüller Nürnberg GmbH 5 94017 06 7 4 Parameter set 0 ...
Страница 85: ...Parameter set 0 Parameters Controller BUS 6 T 79 Baumüller Nürnberg GmbH 5 94017 06 7 4 3 Speed controller ...
Страница 106: ...Maintenance Status messages 100 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 8 2 Status messages ...