Parameters
Parameter set 0
82
Controller BUS 6 T
5.94017.06
Baumüller Nürnberg GmbH
7.4.4 Messages - monitoring
Parameter overview
ID no.
Name
Range
min. ... max.
Unit
Standard
value
Display
only
messages - monitoring
124
speed threshold n
min
6.0000 ... 600.0000
rpm
100
157
velocity window
6.0000 ... 600.0000
rpm
120
125
velocity threshold n
x
6.0000 ... 1200.0000
rpm
100
32829
velocity threshold n
max
1200.0000 ... 12000.0000
rpm
32831
maximum intermediate circuit voltage
threshold
20 ... 800
V
126
torque threshold M
dx
10.0 ... 100.0
%
32830
response time Pzkx (M
dx
)
0.100 ... 30.000
s
32931
voltage failure time
0.000 ... 60.000
s
0
Parameter description
speed threshold n
min
The zero-speed window describes the velocity deviation from n = 0 as an absolute value.
If the actual velocity value is inside the zero-speed window the drive sets the message
n
act
= 0 (ID no. 331).
Display via LED H403 yellow or via relay contacts X3:9 and X3:10 on printed circuit board
3.9211.
velocity window
The drive sets the velocity-dependent messages whenever the measured velocity value
exceeds or falls below the respective velocity comparison value and is inside the velocity
window.
velocity threshold n
x
If the actual velocity value falls below the velocity threshold n
x
, the drive sets the message
n
act
< n
x
(ID no. 332) in Class 3 Diagnostics.
velocity threshold n
max
The maximum permissible ve 10 % is set via this parameter. On exceeding the
threshold the controller is inhibited and and the Class 1 Diagnostics error message set.
maximum intermediate circuit voltage threshold
This parameter is set to the maximum intermediate circuit voltage as standard. On
exceeding the maximum threshold, pulse inhibit takes place.
Содержание BUS 6-T Series
Страница 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 16: ...Type code Technical data 10 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 26: ...Installation Terminal Diagram 20 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 5 4 Terminal diagram I ...
Страница 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Страница 45: ...Initial commissioning Commissioning Controller BUS 6 T 39 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 46: ...Commissioning Initial commissioning 40 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 47: ...Initial commissioning Commissioning Controller BUS 6 T 41 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 49: ...Main spindle area Commissioning Controller BUS 6 T 43 Baumüller Nürnberg GmbH 5 94017 06 PC unit ...
Страница 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...
Страница 56: ...Parameters Basic settings 50 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 7 2 Basic settings ...
Страница 79: ...Parameter set 0 Parameters Controller BUS 6 T 73 Baumüller Nürnberg GmbH 5 94017 06 7 4 Parameter set 0 ...
Страница 85: ...Parameter set 0 Parameters Controller BUS 6 T 79 Baumüller Nürnberg GmbH 5 94017 06 7 4 3 Speed controller ...
Страница 106: ...Maintenance Status messages 100 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH 8 2 Status messages ...