Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
64
4.3
P0895
If the duration of a power loss is less than this parameter setting, the b maXX
®
1000 will
resume operation. If it exceeds the maximum allowable power loss time, the b maXX
®
1000 output is then turned off (coast stop).
The selected operation after power loss in
is only executed when the maximum
allowable power loss time is 5 seconds and the b maXX
®
1000 displays „Lu“.
But if the b maXX
®
1000 is powered off due to overload, even if the maximum allowable
power loss time is 5 seconds, the operation mode as set in
is not executed. In
that case it starts up normally.
P0896
This parameter determines the b maXX
®
1000 restart method after external base block
is enabled.
P0895
Maximal erlaubte Spannungsausfallzeit
0.1 to 5.0 s
EE
Maximum allowable power loss time
2.0 s
STOP
BM_u_DCBrakingDuringStop
10:1
-
P0896
Basis Drehzahlsuche
0 to 2
EE
Base-block speed search
1
STOP
BM_u_BaseBlockSpeedSearch
1:1
-
Value
Meaning
0
Disable speed search
1
Speed search starts with last frequency command
2
Speed search starts with minimum output frequency
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......