Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
109
4
P1163
This parameter sets the voltage range of the analog output signal AFM.
is set to 0, the analog output voltage is directly proportional to the output
frequency of the b maXX
®
set to 100 %, the maximum output fre-
quency
of the b maXX
®
1000 corresponds to +10 V
DC
on the AFM output.
Similarly, if
is set to 1, the analog output voltage is directly proportional to the
output current of the b maXX
®
1000. With
set to 100 %, then 2.5 times the rated
current corresponds to +10 V
DC
on the AFM output.
For Example: When using the meter with full scale of 5 Volts, adjust
is set to 0, then 5 V
DC
will correspond to maximum output frequency.
P1164
This parameter selects the mode of the analog voltage output or analog current output.
Besides parameter settings, the voltage/current mode should be used with the switch.
Figure 49:
Voltage/current mode setting
P1163
Analoges Ausgangssignal Verstärkung
1 to 200 %
EE
Analog output gain
100 %
ON
BM_u_AnalogOutputGain
1:1
NOTE
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 V,
should be set using the following formula:
= ((meter full scale voltage)/10) x 100%
P1164
AO1 Auswahl Ausgang Mode
0 to 2
EE
AO1 terminal mode selection
0
STOP
BM_u_TerminalModeSelectionAO1
1:1
Value
Meaning
0
AVO1 (analog voltage output)
1
ACO1 by 0 to 20 mA (analog current output)
2
ACO1 by 4 to 20 mA (analog current output)
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......