Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
34
4.3
P0122
If temperature exceeds the motor PTC overheat warning level
, the drive will act
according to
hex
. If the temperature decreases be-
low the result (
minus
), the warning display will disappear.
P0123
P0124
Parameters
,
and
can only be changed if
= 0.
P0122
Motorüberhitzung Warnung
0
to 2
EE
Motor PTC overheat warning protection
0
STOP
BM_u_PTCOverheatWarning
1:1
-
Value
Meaning
0
Warn and RAMP to stop
1
Warn and COAST to stop
2
Warn and keep running
P0123
Motor Nenndrehzahl/Nennfrequenz Auswahl
0
to 1
EE
Motor rated speed/nominal slip master selection
1
STOP
BM_u_MotorRatedSpeedSlipSelection
1:1
-
Value
Meaning
0
Motor rated speed is existing, motor rated Slip can automatic calculation with
1
Motor rated slip is existing, motor rated speed can automatic calculation with
P0124
Motor Nenndrehzahl/Nennfrequenz Bestätigung
0
to 2
EE
Motor rated speed/nominal slip master selection
confirm
0
STOP
BM_u_MotorRatedSpeedSlipSelectionConfirm
1:1
-
Value
Meaning
0
Motor nominal slip frequency or motor rated speed can be changed
1
Start calculation
2
Calculated motor nominal slip frequency or motor rated speed OK
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......