B.3
m
Status word
6041
hex
= P0301 (b maXX
®
1000 parameter)
The status word used in the status machine of the unit control
1
)
:
These Bits are low-active.
2)
:
Display operational status
NAME
Index
Sub-index
Data type
Access type
Default
value
Status word
6041
hex
00
hex
U16
RO
0
hex
Bit-No.
Meaning
0
2)
1: ready to operate
0: not ready to operate
1
2)
1: switched on
0: not ready for use
2
2)
1: operation enabled
0: operation inhibited
3
2)
1: error
0: no error
4
1)2)
1: mains voltage/DC-link voltage is present
0: mains voltage/DC-link voltage is not present
5
1)2)
1: no requirements quickstop
0: quickstop (or quickstop requirement is present)
6
2)
1: inhibit start
0: no inhibit start
7
1: warning
0: no warning
8
RFG stop
9
Reserved
10
1: set value reached
0: set value not reached
11
1: internal limit active (for example: current limit, speed limit…)
0: not internal limit active
12
Speed =0, output frequency = 0
13
Reserved
14
Reserved
15
Status synchronous drive = True
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......