Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
73
4
P1076
This parameter defines the time during which the PID feedback must be abnormal before
a warning (see
) is given. It also can be modified according to the system feed-
back signal time.
If this parameter is set to 0.0, the system would not detect any abnormality signal.
P1077
Reaction when the feedback signals (analog PID feedback or PG (encoder) feedback)
are faulty.
P1078
This parameter sets the filter time from the speed feedback to the PG card (pulse gener-
ator, incremental encoder).
P1076
Ansprechzeit PG Geschwindigkeitsrückführung
Signalfehler
0.0 to 10.0 s
EE
Detection time PG speed feedback signal fault
1.0 s
STOP
BM_u_DetectTimePGFault
10:1 s
Value
Meaning
0.0
Disable pulse generator (encoder card) PG
0.1 to 10.0 s
Detection time enabled
P1077
Fehlerbehandlung Geschwindigkeitsrückführung
Signalfehler
0 to 2
EE
Feedback speed signal fault treatment
1
ON
BM_u_FeedbackSignalFaultTreatment
1:1
Value
Meaning
0
Fault and RAMP stop
1
Fault and COAST stop
2
Warn and continue operation
P1078
PG Geschwindigkeitsbewertung Filter
0 to 9999
EE
PG speed estimate filter
1
ON
BM_u_SpeedEstimateFilter
1:2
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......