9.4.
Bus address setting (slaveaddress)
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
PROFIBUS DP 1 (M1B)
SLAVEADDRESS(M1B_0)
Default value:
2
Setting range:
0
to
125
ò
Step by step:
1. Set the selector switch to position
0
(OFF).
2. Press
C
and hold it down for approx. 3 seconds.
Display indicates:
3. Press
q
.
Display indicates:
4. Press
8
.
Display indicates:
5. Select
PROFIBUS DP 1 (M1B)
: Press
q
several times.
Display indicates:
6. Press
8
.
Display indicates:
7. Check setting (view): continue with 8.
Change setting: continue with 11.
48
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Operation instructions
PROFIBUS DP 1
M1B0
VIEW
EDIT
0
I
I
MAIN MENU
M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
MAIN MENU
M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
SETTINGS
M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
SETTINGS
M1B
MONITOR TRIGGERS
POSITIONER
PROFIBUS DP 1