9.2.
Torque switching: check/set
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
TORQUE (M12)
VIEW (M120)
EDIT (M121)
OPENING (M12_0)
CLOSING (M12_1)
Default value:
according to order data
Setting range:
according to torque setting range
refer to actuator name plate
ò
Step by step:
1. Set the selector switch to position
0
(OFF).
2. Press
C
and hold it down for approx. 3 seconds.
Display indicates:
3. Press
q
.
Display indicates:
4. Press
8
.
Display indicates:
5. Press
q
twice.
Display indicates:
42
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Operation instructions
Valve damage due to incorrect setting!
Ò
The torque must suit the valve.
Ò
Only change the setting with the consent of the valve manufacturer.
MAIN MENU
M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
MAIN MENU
M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
0
I
I
SETTINGS
M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
NOTICE
SETTINGS
M12
SET LIMIT SWITCHES
SEATING MODE
TORQUE