9.
Commissioning
Prior to any electrical operation (motor operation), ensure that all commis-
sioning settings described in this clause have been performed.
1. Set the selector switch to position
0
(OFF).
Information
The selector switch is not a mains switch. The actuator control is disabled in
0
(OFF) position. The controls’ power supply is maintained.
2. Switch on the power supply.
3. Perform the settings described in this clause.
Low temperature version
Please note that for low temperature versions, the controls require a heat-up
time.
Heat-up time
This heat-up time is applicable in case the actuator and the controls are not
live and have cooled down to ambient temperature. Under these conditions,
the following heat-up times have been met prior to commissioning after con-
nection to the voltage supply:
For –40 °C = 30 min.
For –50 °C = 60 min.
For –60 °C = 100 min.
Figure 27: Sketch illustrating the heat-up time
38
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Operation instructions
0
30
50
60
0
– 10
– 20
– 30
– 40
– 50
t [min.]
J
[°C]
100
– 60
Figure 27
0
I
I