10.2.2 Status indication S1 - faults
Faults are indicated in this group:
È
Description of the fault indications:
NO FAULT
No fault has occurred.
INTERNAL FAULT
Internal fault has occurred.
For further information:
1. Go to group
D0
: Press
C
and hold it down until diagnostic indication
D0
is displayed.
2. Go to diagnostic indication
D2
: Press
q
twice.
TORQUE FAULT (CLOSE)
Torque fault in direction CLOSE.
Ò
Operation command in direction OPEN, or
Ò
Set selector switch to position
Local control
(LOCAL) and reset fault
indication via
Reset
push button, or
Ò
Issue reset command via fieldbus.
TORQUE FAULT (OPEN)
Torque fault in direction OPEN
Ò
Operation command in direction CLOSE, or
Ò
Set selector switch to position
Local control
(LOCAL) and reset fault
indication via
Reset
push button, or
Ò
Issue reset command via fieldbus.
LOSS OF PHASE
One phase is missing.
Ò
Test/connect phases.
THERMAL FAULT
Motor protection tripped.
Ò
Wait for cooling off.
–
If the fault indication display persists after cooling off:
Set selector switch to position
Local control
(LOCAL) and reset fault
indication via
Reset
push button, or
–
Issue reset command via fieldbus.
Ò
Check fuse F4.
CONFIGURATION FAULT
The controls configuration is incorrect.
For further information:
1. Go to group
D0
: Press
C
and hold it down until diagnostic indication
D0
is displayed.
2. Go to diagnostic indication
D4
: Press
q
four times.
59
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive
Operation instructions
with actuator controls AUMATIC ACExC 01.1 Profibus DP
FAULT IND.
S1
NO FAULT