6.2.
Motor operation
Perform all commissioning settings prior to motor operation.
6.2.1 Local operation
The local operation of the actuator is performed using the push buttons
(figure 23).
Ò
Set selector switch (5) to position
Local control
(LOCAL).
The actuator can now be operated using the push buttons (1 – 3).
1. Run actuator in direction OPEN:
Press push button (1).
2. Stop actuator:
Press push button (2).
3. Run actuator in direction CLOSE.
Press push button (3).
Information
The OPEN - CLOSE operation commands can be given either in
push-to-run operation or in the self-retaining mode.
For further information on this topic refer to “Manual (Operation and setting)
AUMATIC AC 01.1/ACExC 01.1”.
6.2.2 Operation from REMOTE
Ò
Set selector switch to position
Remote control
(REMOTE).
Now, it is possible to operate the actuator by remote control via operation
commands (OPEN, STOP, CLOSE) or via analogue setpoint (e.g. 0 – 20 mA).
Information
Use the
MODE
input (refer to wiring diagram) to select between
REMOTE
MODE
(open-close duty) and
SETPOINT MODE
(modulating duty).
29
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive
Operation instructions
with actuator controls AUMATIC ACExC 01.1 Profibus DP
1
Push button OPEN
4
Reset push button
2
Push button STOP
5
Selector switch
3
Push button CLOSE
6
Indication lights/LEDs
0
I
I
0
I
I
1
6
1
2
3
4
5
STOP
Reset
Figure 23