10.2.4 Status indication S3 - causes for not ready remote
The causes for the
NOT READY IND.
fault signals (status indication
S0
)
are indicated within this group.
È
Description of the fault indications:
READY
Actuator can be operated from REMOTE.
CLEAR STATE
Indicates that the AUMATIC has received a Global Control Clear telegram
via the Profibus DP (the bit can only be deleted with a Global Control Oper-
ate telegram). In this state the actuator cannot be operated from REMOTE.
NOT REMOTE
Actuator
cannot
be operated from REMOTE because the selector switch is
either in position LOCAL or OFF.
WRONG COMMAND
Indicates the fact that several operation commands were received simulta-
neously via Profibus DP (e.g. Remote OPEN and Remote CLOSE simulta-
neously or Remote CLOSE/Remote OPEN and Remote SETPOINT (nomi-
nal) simultaneously) or that the max. value for a nominal position has been
exceeded.
EMERGENCY MODE
The EMERGENCY operation mode is active.
EXTERNAL CONTROLS
For combination fieldbus/standard interface function:
Operation via parallel interface.
EMCY STOP ACTIVE
The EMERGENCY STOP button has been operated.
ACTUATOR LOCKED
Actuator locked (only set for special applications e.g. for by-pass function).
62
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Operation instructions
NOT READY IND.
S3
READY