9.3.
Limit switching setting
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SET LIMIT SWITCHES (M10)
CLOSED POSITION (M101)
OPEN POSITION (M101)
ò
Step by step:
1. Set the selector switch to position
0
(OFF).
2. Press
C
and hold it down for approx. 3 seconds.
Display indicates:
3. Press
q
.
Display indicates:
4. Press
8
.
Display indicates:
5. Press
8
.
Display indicates:
6. Enter password:
Press
8
4 times = 0000 (default factory password).
The current actuator position is displayed:
p q
are used to change between the
CLOSED POSITION
(left figure)
and
OPEN POSITION
(right figure) displays.
45
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive
Operation instructions
with actuator controls AUMATIC ACExC 01.1 Profibus DP
MAIN MENU
M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
MAIN MENU
M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
0
I
I
SETTINGS
M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
ENTER PASSWORD
0 * * *
:EDIT
¿
:OK C:ESC
SET LIMIT SWITC
M101
OPEN POSITION
63.3 %
¿
:EDIT
C:ESC
SET LIMIT SWITC
M100
CLOSED POSITION
63.3 %
¿
:EDIT
C:ESC