9.6.
Switch compartment: open
The switch compartment must be opened to perform the following settings
(options).
1. Loosen screws (2) and remove cover (1) from the switch compartment.
9.7.
Mechanical position indicator setting (option)
1. Move valve to end position CLOSED.
2. Turn lower indicator disc until
symbol (CLOSED) is in alignment
with the
p
mark on the cover.
3. Move actuator to end position OPEN.
4. Hold lower indicator disc CLOSED in position and turn upper disc
with
symbol (OPEN) until it is in alignment with the
p
mark on
the cover.
5. Move valve to end position CLOSED again.
6. Check settings: If the
symbol (CLOSED) is no longer in alignment
with
p
mark on the cover:
Ò
Test/set gear stage of the reduction gearing (page 54).
7. If the setting is correct: Close switch compartment (see page 56.
53
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive
Operation instructions
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Ò
Before opening, ensure that there is no explosive gas and no voltage.
Ò
Handle cover and housing parts with care.
Ò
Joint surfaces must not be damaged or soiled in any way.
Ò
Do not jam cover during fitting.
DANGER