7. Setting end position CLOSED: continue with 8
Setting end position OPEN: continue with 13
Setting end position CLOSED
8. Press
8
to enter the edit mode:
Display indicates:
9. Engage manual operation.
10. Turn handwheel clockwise until valve is closed.
11. Turn handwheel back by approximately half a turn (overrun).
12. Press
8
to accept new end position.
LEDs and display indicate that the new end position has been accepted:
–
The left LED is illuminated (standard setting).
–
Display indicates: 0.0 %.
q
is used to select
OPEN POSITION
.
Setting end position OPEN
13. Press
8
to enter the edit mode:
Display indicates:
14. Engage manual operation.
15. Turn handwheel counterclockwise until valve is open.
16. Turn handwheel back by approximately half a turn (overrun).
17. Press
8
to accept new end position.
LEDs and display indicate that the new end position has been accepted:
–
The right LED is illuminated (standard setting).
–
Display indicates: 100.0 %.
q
is used to select
CLOSED POSITION
.
18. Press
C
several times until
S0
is displayed to return to the status indication.
46
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Operation instructions
SET LIMIT SWITC
M101
OPEN POSITION
¿
:ACCEPT
C:ESC
SET LIMIT SWITC
M100
CLOSED POSITION
¿
:ACCEPT
C:ESC
SET LIMIT SWITC
M100
CLOSED POSITION
0.0 %
¿
:EDIT
C:ESC
SET LIMIT SWITC
M101
OPEN POSITION
100.0 %
¿
:EDIT
C:ESC