P846/EN ST/D
Settings
(ST) 4-14
MiCOM P846
ST
1.3.7
Commissioning tests
There are menu cells which allow the status of the opto-isolated inputs, output relay
contacts, internal digital data bus (DDB) signals and user-programmable LEDs to be
monitored. Additionally there are cells to test the operation of the output contacts, user-
programmable LEDs and, where available, the auto-reclose cycles.
Menu Text
Default Setting
Available Settings
COMMISSION TESTS
Opto I/P Status
0000000000000000
This menu cell displays the status of the relay’s opto-isolated inputs as a binary string, a ‘1’
indicating an energized opto-isolated input and a ‘0’ a de-energized one
Relay O/P Status
0000000000000000
This menu cell displays the status of the digital data bus (DDB) signals that result in
energization of the output relays as a binary string, a ‘1’ indicating an operated state and
‘0’ a non-operated state.
When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the
current status of the output relays and hence can not be used to confirm operation of the
output relays. Therefore it will be necessary to monitor the state of each contact in turn.
Test Port Status
00000000
This menu cell displays the status of the eight digital data bus (DDB) signals that have
been allocated in the ‘Monitor Bit’ cells.
LED Status
000000000000000000
This cell is an eighteen bit binary string that indicates which of the user-programmable
LEDs on the relay are illuminated with the input active when accessing the relay from a
remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.
Monitor Bit 1
64 (LED 1)
0 to 511
See PSL chapter for
details of digital data
bus signals
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus
signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.
Monitor Bit 8
71 (LED 8)
0 to 511
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus
signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.
Test Mode
Disabled
Disabled, Test Mode,
Contacts Blocked
The Test Mode menu cell is used to allow secondary injection testing to be performed on
the relay without operation of the trip contacts. It also enables a facility to directly test the
output contacts by applying menu controlled test signals. To select test mode the Test
Mode menu cell should be set to ‘Test Mode’, which takes the relay out of service and
blocks operation of output contacts and maintenance, counters. It also causes an alarm
condition to be recorded and the yellow ‘Out of Service’ LED to illuminate and an alarm
message ‘Prot’n. Disabled’ is given.
To enable testing of output contacts the Test Mode cell should be set to Contacts Blocked.
This blocks the protection from operating the contacts and enables the test pattern and
contact test functions which can be used to manually operate the output contacts. Once
testing is complete the cell must be set back to ‘Disabled’ to restore the relay back to
service.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......