Operation
P846/EN OP/D
MiCOM P846
(OP) 5-17
OP
−
Circuit Breaker (CB) is defective
ormally
open / normally closed output contact can be assigned to this function via the programmable
during normal
ROL
relay menu there is a setting called ‘CB Status Input’.
owing options:
None
52A
52B 3 pole
52A
52A
52B
52A & 52B 1 pole
Should both sets of contacts be closed, only one of the following two conditions would apply:
−
Auxiliary contacts / wiring defective
If any of the above conditions exist, an alarm will be issued after a 5s time delay. A n
scheme logic (PSL). The time delay is set to avoid unwanted operation
switching duties.
In the CB CONT
column of the
This cell can be set at one of the foll
3 pole
& 52B 3 pole
1 pole
1 pole
Selection of the inputs used for CB status is user definable in the CB Status Input cell under
nu. The inputs used to determine the circuit breakers status can be either
ntacts for single or three pole and for one circuit breaker or for two circuit
nputs via the PSL.
Auxiliary Contact Position
CB State Detected
Action
the CB control me
52a and/or 52b co
breakers in the case of the P846.
Where ‘None’ is selected no CB status will be available. This will directly affect any function
within the relay that requires this signal, for example CB control, auto-reclose, etc. Where
only 52A is used on its own then the relay will assume a 52B signal from the absence of the
52A signal. Circuit breaker status information will be available in this case but no
discrepancy alarm will be available. The above is also true where only a 52B is used. If
both 52A and 52B are used then status information will be available and in addition a
discrepancy alarm will be possible, according to the following table. 52A and 52B inputs are
assigned to relay opto-isolated i
52A 52B
Open
Closed
Breaker Open
Circuit breaker healthy
Closed
Open
Breaker Closed
Circuit breaker healthy
Closed
Closed
CB
Failure
Alarm raised if the condition
persists for greater than 5s
Open
Open
State
Unknown
Alarm raised if the condition
persists for greater than 5s
Table 1.
Where single pole tripping is used (available on certain relays only) then an open breaker
condition will only be given if all three phases indicate and open condition. Similarly for a
closed breaker condition indication that all three phases are closed must be given. For
single pole tripping applications 52A-a, 52A-b and 52A-c and/or 52B-a, 52B-b and 52B-c
inputs should be used.
In the case of the P846 two circuit breakers are monitored. If inputs relevant to each of the
circuit breaker’s (CB1 and CB2) are available to the relay via the opto isolated inputs it will
be able to determine the state of each circuit breaker.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......