P846/EN ST/D
Settings
(ST) 4-16
MiCOM P846
ST
Setting Range
Menu Text
Default Setting
Min. Max.
Step Size
Opto Input 1
24 - 27
24 - 27, 30 - 34, 48 - 54, 110 - 125,
220 - 250
Each opto input can individually be set to a nominal voltage value if custom is selected for
the global setting.
Opto Input 2 - 24
24 - 27
24 - 27, 30 - 34, 48 - 54, 110 - 125,
220 - 250
Each opto input can individually be set to a nominal voltage value if custom is selected for
the global setting.
Characteristics
Standard
60% - 80%
Standard 60% - 80%, 50% - 70%
Selects the pick-up and drop-off characteristics of the optos. Selecting the standard
setting means they nominally provide a Logic 1 or On value for Voltages
≥
80% of the set
lower nominal voltage and a Logic 0 or Off value for the voltages
≤
60% of the set higher
nominal voltage.
1.3.9
Control input configuration
The control inputs function as software switches that can be set or reset either locally or
remotely. These inputs can be used to trigger any function that they are connected to as
part of the PSL.
Menu Text
Default Setting
Setting Range
Step Size
CTRL I/P CONFIG.
Hotkey Enabled
11111111111111111111111111111111
Setting to allow the control inputs to be individually assigned to the “Hotkey” menu by
setting ‘1’ in the appropriate bit in the “Hotkey Enabled” cell. The hotkey menu allows the
control inputs to be set, reset or pulsed without the need to enter the “CONTROL INPUTS”
column
Control Input 1
Latched
Latched, Pulsed
Configures the control inputs as either ‘latched’ or ‘pulsed’. A latched control input will
remain in the set state until a reset command is given, either by the menu or the serial
communications. A pulsed control input, however, will remain energized for 10ms after the
set command is given and will then reset automatically (i.e. no reset command required).
Ctrl Command 1
Set/Reset
Set/Reset, In/Out, Enabled/Disabled,
On/Off
Allows the SET / RESET text, displayed in the hotkey menu, to be changed to something
more suitable for the application of an individual control input, such as “ON / OFF”, “IN /
OUT” etc.
Control Input 2 to 32
Latched
Latched, Pulsed
Configures the control inputs as either ‘latched’ or ‘pulsed’.
Ctrl Command
2 to 32
Set/Reset
Set/Reset, In/Out, Enabled/Disabled,
On/Off
Allows the SET / RESET text, displayed in the hotkey menu, to be changed to something
more suitable for the application of an individual control input, such as “ON / OFF”, “IN /
OUT” etc.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......