P846/EN CM/D
Commissioning
(CM) 10-24
MiCOM P846
7.1.2
Current connections
Measure the current transformer secondary values for each input using a multimeter
connected in series with the corresponding relay current input.
Check that the current transformer polarities are correct by measuring the phase angle
between the current and voltage, either against a phase meter already installed on site and
known to be correct or by determining the direction of power flow by contacting the system
control center.
Ensure the current flowing in the neutral circuit of the current transformers is negligible.
Compare the values of the secondary phase currents and phase angle with the relay’s
measured values, which can be found in the MEASUREMENTS 1 menu column.
If cell [0D02: MEASURE’T. SETUP, Local Values] is set to ‘Secondary’, the currents
displayed on the LCD or a portable PC connected to the front EIA(RS)232 communication
port of the relay should be equal to the applied secondary current. The values should be
within 1% of the applied secondary currents. However, an additional allowance must be
made for the accuracy of the test equipment being used.
If cell [0D02: MEASURE’T. SETUP, Local Values] is set to ‘Primary’, the currents displayed
on the relay should be equal to the applied secondary current multiplied by the
corresponding current transformer ratio set in ‘CT & VT RATIOS’ menu column (see Table
9). Again the values should be within 1% of the expected value, plus an additional
allowance for the accuracy of the test equipment being used.
7.2
On load directional test
This test is important to ensure that open line detector function has the correct
forward/reverse response to load conditions.
Firstly the actual direction of power flow on the system must be ascertained, using adjacent
instrumentation or protection already in-service, or a knowledge of the prevailing network
operation conditions.
−
For load current flowing in the Forward direction - i.e. power export to the remote line
end, cell [0301: MEASUREMENTS 2, A Phase Watts] should show
positive
power
signing.
CM
−
For load current flowing in the Reverse direction - i.e. power import from the remote line
end, cell [0301: MEASUREMENTS 2, A Phase Watts] should show
negative
power
signing.
Note:
The check above applies only for Measurement Modes 0 (default),
and 2. This should be checked in [0D05: MEASURE’T. SETUP,
Measurement Mode = 0 or 2]. If measurement modes 1 or 3 are
used, the expected power flow signing would be opposite to that
shown in the bullets above.
In the event of any uncertainty, check the phase angle of the phase currents with respect to
the their phase voltage.
uncertainty, check the phase angle of the phase currents with respect to
the their phase voltage.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......