P846/EN MT/D
Maintenance
(MT) 11-4
MiCOM P846
1.3
Method of repair
1.3.1
MiCOM P846 relay
If the relay should develop a fault whilst in service, depending on the nature of the fault, the
watchdog contacts will change state and an alarm condition will be flagged. Due to the
extensive use of surface-mount components faulty PCBs should be replaced, as it is not
possible to perform repairs on damaged circuits. Thus either the complete relay or just the
faulty PCB, identified by the in-built diagnostic software, can be replaced. Advice about
identifying the faulty PCB can be found in the Troubleshooting section (P846/EN TS).
The preferred method is to replace the complete relay as it ensures that the internal circuitry
is protected against electrostatic discharge and physical damage at all times and overcomes
the possibility of incompatibility between replacement PCBs. However, it may be difficult to
remove an installed relay due to limited access in the back of the cubicle and rigidity of the
scheme wiring.
Replacing PCBs can reduce transport costs but requires clean, dry conditions on site and
higher skills from the person performing the repair. However, if the repair is not performed
by an approved service center, the warranty will be invalidated.
Before carrying out any work on the equipment, the user should be familiar with the
contents of the Safety and Technical Data sections and the ratings on the equipment’s
rating label. This should ensure that no damage is caused by incorrect handling of
the electronic components.
1.3.1.1 Replacing the complete relay
The case and rear terminal blocks have been designed to facilitate removal of the complete
relay should replacement or repair become necessary without having to disconnect the
scheme wiring.
Before working at the rear of the relay, isolate all voltage and current supplies to the relay.
Note:
The MiCOM range of relays have integral current transformer shorting
switches which will close when the heavy duty terminal block is
removed.
Disconnect the relay earth, IRIG-B and fiber optic connections, as appropriate, from the rear
of the relay.
MT
terminal block, they are labeled alphabetically with ‘A’ on the left hand side when viewed
from the rear.
There are two types of terminal block used on the relay, medium and heavy duty, which are
fastened to the rear panel using crosshead screws, as in Figure 1 of the Commissioning
section (P846/EN CM).
Note:
The use of a magnetic bladed screwdriver is recommended to
minimize the risk of the screws being left in the terminal block or lost.
Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks
away from their internal connectors.
Remove the screws used to fasten the relay to the panel, rack, etc. These are the screws
with the larger diameter heads that are accessible when the access covers are fitted and
open.
If the top and bottom access covers have been removed, do not remove the screws
with the smaller diameter heads which are accessible. These screws secure the front
panel to the relay.
Withdraw the relay carefully from the panel, rack, etc. because it will be heavy due to the
internal transformers.
To reinstall the repaired or replacement relay, follow the above instructions in reverse,
ensuring that each terminal block is relocated in the correct position and the case earth,
IRIG-B and fiber optic connections are replaced. To facilitate easy identification of each
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......