P846/EN PL/D
Programmable Logic
(PL) 7-12
MiCOM P846
PL
1.7
Description of logic nodes
DDB No.
English Text
Source
Description
0
Output Label 1 (settable)
Output Conditioner
Signal which shows the state of output relay 1
(0 = de-energized, 1 = energized)
1 - 31
Output Label 2 … 32
(settable)
Output Conditioner
Signal which shows the state of output relay 2 to 32
(0 = de-energized, 1 = energized)
32
Opto Label 1 (settable)
Opto Input
Signal which shows the state of opto input 1
(0 = de-energized, 1 = energized)
33 - 55
Opto Label 2 … 31
(settable)
Opto Input
Signal which shows the state of opto input 2 to 32
(0 = de-energized, 1 = energized)
56 - 63
Reserved
64
LED 1
Output Conditioner
Signal which shows the state of programmable LED 1
(0 = Off; 1 = On)
65 - 71
LED 2 … 8
Output Conditioner
Signal which shows the state of programmable LED 2
to 8. (0 = Off; 1 = On)
72
LED Cond IN 1
PSL
Input to LED Output Condition 1
73 - 79
LED Cond IN 2 … 8
PSL
Input to LED Output Condition 2 to 8
80 - 95
Reserved
95
Relay Cond. 1
PSL
Input to Relay Output conditioner 1
96 - 127
Relay Cond. 2 … 32
PSL
Input to Relay Output conditioner 2 to 32
104
LED Cond. IN 1
PSL
Input to programmable LED conditioner 1
105 - 111
LED Cond. IN 2 … 8
PSL
Input to programmable LED conditioner 2 to 8
128
Timer in 1
PSL
Input to Auxiliary Timer 1
129 - 143
Timer in 2 … 16
PSL
Input to Auxiliary Timer 2 to 16
144
Timer out 1
Auxiliary Timer
Output from Auxiliary Timer 1
145 - 159
Timer out 2 … 16
Auxiliary Timer
Output from Auxiliary Timer 2 to 16
160
Control Input 1
Control Input Command
Control Input 1 - for SCADA and menu commands into
PSL
161 - 191
Control Input 2 … 32
Control Input Command
Control Input 2 to 32 - for SCADA and menu
commands into PSL
192 - 255
Reserved
256
SG-opto Invalid
Group Selection
Setting group selection opto inputs have detected an
invalid (disabled) settings group
257 Prot'n.
Disabled
Commissioning
Test
Protection disabled - typically out of service due to test
mode
258
VT Fail Alarm
VT Supervision
VTS Indication alarm- failed VT (fuse blow) detected
by VT supervision
259 |Reserved
260
CVT Alarm
CVT Logic
CVT indication alarm active when the Vp or Vn voltage
has fallen below the set threshold.
261
CB Fail Alarm
CB Fail
Circuit Breaker Fail Alarm
262 - 268
Reserved
269
CB Status Alarm
CB Status
Indication of problems by Circuit Breaker state
monitoring - example defective auxiliary contacts
270
CB Trip Fail
CB Control
Circuit Breaker Failed to Trip (after a manual/operator
trip command)
271
CB Close. Fail
CB Control
Circuit Breaker Failed to Close (after a
manual/operator or auto-reclose close command)
272
Man CB Unhealthy
CB Control
Manual Circuit Breaker Unhealthy Output signal
indicating that the circuit breaker has not closed
successfully after a manual close command. (A
successful close also requires The Circuit Breaker
Healthy signal to reappear within the "healthy window"
timeout)
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......