P846/EN CM/D
Commissioning
(CM) 10-20
MiCOM P846
6.
SETTING CHECKS
The setting checks ensure that all of the application-specific relay settings (i.e. both the
relay’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the relay.
If the application-specific settings are not available, ignore sections 6.1 and 6.2.
Note:
The trip circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
6.1
Apply application-specific settings
There are two methods of applying the settings to the relay:
Transferring them from a pre-prepared setting file to the relay using a portable PC running
the appropriate software via the relay’s front EIA(RS)232 port, located under the bottom
access cover, or rear communications port (with a KITZ protocol converter connected). This
method is preferred for transferring function settings as it is much faster and there is less
margin for error. If programmable scheme logic other than the default settings with which
the relay is supplied are to be used then this is the only way of changing the settings.
If a setting file has been created for the particular application and provided on a diskette, this
will further reduce the commissioning time and should always be the case where
application-specific programmable scheme logic is to be applied to the relay.
Enter them manually via the relay’s operator interface. This method is not suitable for
changing the programmable scheme logic.
Note:
It is essential that where the installation needs application-specific
Programmable Scheme Logic, that the appropriate .psl file is
downloaded (sent) to the relay, for each and every setting group that
will be used. If the user fails to download the required .psl file to any
setting group that may be brought into service, then factory default
PSL will still be resident. This may have severe operational and
safety consequences.
6.2
Demonstrate correct relay operation
Tests 5.2.9 and 5.2.10 have already demonstrated that the relay is within calibration, thus
the purpose of these tests is as follows:
CM
−
To determine that the primary protection functions of the relay can trip according to the
correct application settings.
−
To verify correct assignment of the trip contacts, by monitoring the response to a
selection of fault injections.
6.2.1
Open line detector protection testing
This test, performed on the DLO protection function in setting group 1, demonstrates that the
relay is operating correctly at the application-specific settings.
6.2.1.1 Connection and preliminaries
Determine which output relay has been selected to operate when an ‘Open Line Detect’ trip
occurs by viewing the relay’s programmable scheme logic.
The programmable scheme logic can only be changed using the appropriate software. If this
software has not been available then the default output relay allocations will still be
applicable.
The associated terminal numbers can be found from the external connection diagram
(P846/EN IN).
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......