Commissioning
P846/EN CM/D
MiCOM P846
(CM) 10-23
7.
ON-LOAD CHECKS
The objectives of the on-load checks are to:
−
Confirm the external wiring to the current and voltage inputs is correct.
−
Check the polarity of the line current transformers at each end is consistent.
However, these checks can only be carried out if there are no restrictions preventing the
energization of the plant being protected and the other P846 relays in the group have been
commissioned.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that
has been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the relay in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram.
7.1
Confirm current and voltage transformer wiring
7.1.1
Voltage connections
Using a multimeter measure the voltage transformer secondary voltages to ensure they are
correctly rated. Check that the system phase rotation is correct using a phase rotation
meter.
Compare the values of the secondary phase voltages with the relay’s measured values,
which can be found in the MEASUREMENTS 1 menu column.
Voltage
Cell in MEASUREMENTS 1
column (02)
Corresponding VT Ratio in ‘VT
and CT RATIO‘ column (0A) of
menu)
VAB
VBC
VCA
VAN
VBN
VCN
[0214: VAB Magnitude]
[0216: VBC Magnitude]
[0218: VCA Magnitude]
[021A: VAN Magnitude]
[021C: VBN Magnitude]
[021E: VCN Magnitude]
Error! Bookmark not
defined.Error! Bookmark not
defined.
[0A01 : Main VT Primary]
[0A02 : Main VT Secondary]
CM
Table 10:
Measured voltages and VT ratio settings
If cell [0D02: MEASURE’T. SETUP, Local Values] is set to ‘Secondary’, the values displayed
on the relay LCD or a portable PC connected to the front EIA(RS)232 communication port
should be equal to the applied secondary voltage. The values should be within 1% of the
applied secondary voltages. However, an additional allowance must be made for the
accuracy of the test equipment being used.
If cell [0D02: MEASURE’T. SETUP, Local Values] is set to ‘Primary’, the values displayed
should be equal to the applied secondary voltage multiplied the corresponding voltage
transformer ratio set in the ‘CT & VT RATIOS’ menu column (see Table 10). Again the
values should be within 1% of the expected value, plus an additional allowance for the
accuracy of the test equipment being used.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......