336
Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
Chapter 5
Troubleshoot the Switch
Reset the Switch via the Express Setup Button
Restart the Switch from the Logix Designer Application
From Module Properties dialog box within the Studio 5000 Logix Designer®
application, do the following.
1.
In the navigation pane, click Module Info.
2.
To restart the switch and maintain the current configurations, click
Reset Module.
A password prompt appears.
3.
Enter your password and click Enter.
Troubleshoot a
Firmware Update
If you attempted to update the switch firmware but received a message that the
update failed, make sure that you still have access to the switch. If you still have
switch access, follow these steps.
1.
Make sure that you downloaded the correct .tar file.
2.
If you downloaded the correct .tar file, refresh the browser session for
Device Manager to verify connectivity between the switch and your
computer or network drive.
•
If you have connectivity to the switch and Device Manager, retry the
update.
•
If you do not have connectivity to the switch and Device Manager,
Restart or Reset the Switch on page 335
.
IOS Release
Switch
Reset Procedure
15.2(4)EA3 or later
All
Press and hold the Express Setup button until the Setup status indicator flashes alternating green and red during seconds
16…20, and then release.
See also
Run Multi-mode Express Setup in Long Press Mode on page 33
15.2(4)EA or earlier
Stratix 5400, 5410, 5700,
or ArmorStratix™ 5700
Follow these steps.
1. Make sure that the switch is fully powered up.
2. Press and hold the Express Setup button for 10 seconds until the EIP Mod status indicator turns red, and then immediately
release the Express Setup button.
IMPORTANT:
If you hold the Express Setup button too long (approximately 20 seconds), the EIP Net and EIP Mod status
indicators turn red and the switch begins the power-on sequence. If this scenario occurs, power off and restart the switch to
return to the factory default settings.
Stratix 8000 or 8300
Follow these steps.
1. Remove power from the switch.
2. Reapply power to the switch.
3. While the switch is powering up, press and hold the Express Setup button.
4. When the EIP Mod, EIP Net and Setup status indictors turn red, release the Express Setup button.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......