
Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
247
Configure Switch Features
Chapter 3
Table 95 - CLI Commands to Enable PROFINET
Command
Description
Step 1
profinet
Enables PROFINET on the switch.
Step 2
profinet id [PROFINET device name]
Sets the PROFINET device identifier (ID).
IMPORTANT:
This ID must match the PROFINET device name you specified for the switch in your controller project.
The maximum length is 240 characters. The only special characters allowed are the period (.) and hyphen (-), and they are
allowed only in specific positions within the ID string. It can have multiple labels within the string. Each label can be from
1 to 63 characters, and labels must be separated by a period (.). The final character in the string must not be zero (0).
For more details about configuring the PROFINET ID, see the PROFINET specification, document number TC2-06-0007a,
filename PN-AL-protocol_2722_V22_Oct07, available from
.
Step 3
profinet vlan [vlan id]
(Optional). Changes the VLAN number. The default VLAN number is 1. The VLAN ID range is 1…4094.
Step 4
end
Returns to privileged EXEC mode.
Step 5
show running-config
Verifies your entries.
Step 6
copy running-config startup-config
(Optional). Saves your entries in the configuration file.
Example
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......