328
Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
Chapter 4
Monitor the Switch
Diagnose Cables via the Logix Designer Application
In the navigation pane, click Port Status, and then click the button in the Cable
Diagnostics column for the corresponding port.
Table 127 - Cable Diagnostics Fields
Field
Description
Port
The port that is selected for configuration. The port number includes the port type (Fa for Fast Ethernet and Gi for Gigabit Ethernet), and the
specific port number.
EXAMPLE:
Gi1/1 is Gigabit Ethernet port 1.
Test last run on
The time the test was last executed. The date time format is mm/dd/yy hh:mm:ss tt. If the test has never been run, the time and all distance and
status information is blank.
Pair
Each pair of cables in the network individually listed. If pair does not exist or test has never beeto indicate run, this field is blank.
Status
Specifies the link state the last time the test was executed. If pair does not exist or test has never run, status is blank. For distance, if the pair is
Normal status, ‘No Break Detected’ is shown. No distance is displayed.
Distance to Break
The distance to the break from the switch for each estimated pair with a plus or minus error value individually listed. A value is displayed only
when the status of an existing pair is not Normal. This field is blank if the test was never run before. If a pair does not exist, ‘???’ appears.
Diagnose Cable
Click to run the Diagnose Cable test. A connection interruption warning appears:
•
If you are sure that you want to continue with the test, click Yes. Be prepared to enter a valid password to run the test.
•
If you do not want to run the test, click No or close the page.
IMPORTANT:
To run a valid test on gigabit ports, you must first configure the gigabit port as an RJ45 media type in Device Manager as described
in
Configure Port Settings on page 49
.
IMPORTANT:
This test can interrupt connections to the module and to any other modules connected through this module. Also, the connection
between workstation and controller can be interrupted. You must have the correct privilege to run this test.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......