Chapter 3
Configure Switch Features
Delay Request
The logarithmic mean interval in seconds.
Type the recommended to connected devices to send delay request messages when the switch port is in the master state.
Valid values:
•
-1—half second
•
0—1 second
•
1—2 seconds
•
2—4 seconds
•
3—8 seconds
•
4—16 seconds
•
5—32 seconds
•
6—64 seconds
Default: 5 (32 seconds)
Announce Timeout
Type the number of announce intervals, specified as the logarithmic mean in seconds, that must pass without receipt of an announce message
from the parent or Grandmaster clock before the switch selects a new parent or Grandmaster clock.
Valid values: 2…10
Default: 3 (8 seconds)
Announce Interval
Type the time interval, specified as the logarithmic mean in seconds, for sending announce messages.
Valid values:
•
0—1 second
•
1—2 seconds
•
2— 4 seconds
•
3— 8 seconds
•
4—16 seconds
Default: 1 (2 seconds)
Sync Interval
Type the time interval, specified as the logarithmic mean in seconds, for sending synchronization messages.
Valid values:
•
-1—half second
•
0—1 second
•
1— 2 seconds
Default: 0 (1 second)
Sync Fault Limit
Type the maximum clock offset before PTP attempts to reacquire synchronization.
Valid values: 50…500000000 nanoseconds
Default: 50000 nanoseconds
IMPORTANT:
We recommend against setting the sync limit below the default (50000 nanoseconds). Use values below 50000 nanoseconds
only in networks with a very high-precision Grandmaster clock. These networks have a critical need to keep very sensitive devices
synchronized.
Table 32 - Boundary Mode (Continued)
Field
Description
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......