86
Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
Chapter 3
Configure Switch Features
Before you configure a switch to use NTP-PTP clock mode, do the following:
•
Configure NTP as described on
. While NTP-PTP Clock
mode requires only one NTP time source, as a best practice, we
recommend you configure two or more NTP time sources.
•
Make sure the NTP clock is stable.
•
Know the priority settings assigned to other PTP devices, so that you
can set up the switch as the Grandmaster.
Configure Time Synchronization via Device Manager
1.
From the Configure menu, choose PTP.
2.
From the Mode pull-down menu, choose a mode.
The modes and fields shown in the following figure vary based on the
switch model and mode setting.
3.
Complete the following fields, and then click Submit.
Field
Description
Priority 1
(Boundary or NTP-PTP Clock mode). Type a value to override the default criteria (clock
quality, clock class, and so on) for the best master clock selection. A lower value takes
precedence.
Valid values: 0…255
Default: 128
Priority 2
(Boundary or NTP-PTP Clock mode). Type a value to use as a tie-breaker between two
devices that are otherwise equally matched in the default criteria. For example, you can
give a specific switch priority over other identical switches. A lower value takes
precedence.
Valid values: 0…255
Default: 128
Clock Identity
Displays a unique identifier for the clock.
Offset From Master (ns)
Displays the time offset in nanoseconds between the slave and master clocks.
Passthrough
(Stratix 8000/8300
switches)
(Boundary or End to End Transparent mode). Check the checkbox to enable PTP pass-
through processing.
After PTP pass-through is enabled, all PTP messages are passed to and from the
expansion module ports in the VLAN on which the packets are received. The PTP pass-
through feature is not compatible with the virtual routing and forwarding (VRF), policy-
based routing (PBR), and private virtual local area network (PVALN) features.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......