Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
Chapter 3
Configure Switch Features
Use SNMP Management Applications
You can use SNMP management applications such as IntraVue or HP
OpenView to configure and manage the switch.
Management Protocol (SNMP) on page 259
for more information.
Smartports
Smartports are recommended configurations for switch ports. These
configurations, referred to as port roles, optimize the switch connections and
provide security, transmission quality, and reliability for traffic from the switch
ports. Port roles also help to prevent port misconfigurations.
Use Smartport roles immediately after the initial setup of the switch to
configure the switch ports before they connect to devices.
Follow these guidelines when using Smartport roles:
•
Before using Smartport roles, decide which switch port is connected to
which device type.
•
Before attaching a device to the port or reconnecting devices that have
been moved, verify which Smartport role is applied to a port.
•
You cannot configure port roles on routed ports.
The port roles that are described in
are based on the type of devices to
be connected to the switch ports. For example, the Desktop for Automation
port role is specifically for switch ports to be connected to desktop and laptop
computers.
IMPORTANT
We recommend that you do not change port settings after enabling
a Smartport role on a port. Any port setting changes can alter the
effectiveness of the Smartport role.
Table 99 - Smartport Roles
Port Role
Description
Automation Device
Apply this role to ports to be connected to EtherNet/IP (Ethernet Industrial Protocol) devices. It can be used for industrial automation devices,
such as logic controllers and I/O:
•
Port is set to Access mode.
•
Port security supports only one MAC ID.
•
Optimize queue management for CIP traffic.
Multiport Automation Device
Apply this role to DLR-enabled ports and ports connected to multiport EtherNet/IP devices. Devices include multiport EtherNet/IP devices
arranged in a linear or daisy chain topology, the 1783-ETAP module (for connection to only the device port), unmanaged switches, such as the
Stratix 2000, and managed switches with Remote Spanning Tree Protocol (RSTP) disabled:
•
Port is set to Access mode.
•
No port security.
•
Optimized queue management for CIP traffic.
Desktop for Automation
Apply this role to ports to be connected to desktop devices, such as desktop computers, workstations, notebook computers, and other
client-based hosts:
•
Port is set to Access mode.
•
PortFast enabled.
•
Port security supports only one MAC ID.
Do not apply to ports to be connected to switches, routers, or access points.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......