Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
95
Configure Switch Features
Chapter 3
Figure 5 - Boundary Mode
Table 32 - Boundary Mode
Field
Description
Clock Identity
Displays a unique identifier for the clock.
Grandmaster Selection Priority1
Type a value to override the default criteria (clock quality, clock class, and so on) for the best master clock selection. A lower value takes
precedence.
Valid values: 0…255
Default: 128
Grandmaster Selection Priority 2
Type a value to use as a tie-breaker between two devices that are otherwise equally matched in the default criteria. For example, you can give
a specific switch priority over other identical switches. A lower value takes precedence.
Valid values: 0…255
Default: 128
Offset from Master
Displays the time offset in nanoseconds between the slave and master clocks.
Port
Displays the port type and port number:
•
Fa—Fast Ethernet
•
Gi—Gigabit Ethernet
•
Te—10 Gigabit Ethernet
Enable
Check the checkbox for each port on which to enable PTP. You can enable one or more switch ports.
By default, PTP is enabled on all the Fast Ethernet and Gigabit Ethernet ports.
For Stratix 8000/8300 switches, only the ports on the base switch module are PTP-capable. The switch expansion modules do not support PTP.
State
Displays the synchronization state of the switch port with the parent or Grandmaster clock:
•
Initializing—The switch port is waiting while a parent or Grandmaster clock is selected.
•
Listening—The switch port is waiting while a parent or Grandmaster clock is selected.
•
Pre-master—The switch port is transitioning to change to Master state.
•
Master—The switch is acting as a parent clock to the devices connected to that switch port.
•
Passive—The switch has detected a redundant path to a parent or Grandmaster clock. For example, two different switch ports claim the
same parent or Grandmaster clock. To help prevent a loop in the network, one of the ports changes to Passive state.
•
Uncalibrated—The switch port cannot synchronize with the parent or Grandmaster clock.
•
Slave—The switch port is connected to and synchronizing with the parent or Grandmaster clock.
•
Faulty—Either PTP is not operating properly on the switch port or nothing is connected to the port.
•
Disabled—PTP is not enabled on the switch port.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......