Configure Switch Features
Chapter 3
To change the default settings after adding an EIGRP instance, on the EIGRP
Instances tab, click the button in the row to customize, and then click
Customize Default Settings.
Loading
Type a number that represents the effective bandwidth of the route.
Valid values: 1…255 where 255 is 100 percent loading
MTU
Type the smallest allowed value for the maximum transmission unit (MTU) in bytes.
Valid values: 1…65535
Static Neighbor
—EIGRP hello packets are sent as multicast packets. If an EIGRP neighbor is located across a nonbroadcast network, such as a tunnel, you must manually define
that neighbor. When you manually define an EIGRP neighbor, hello packets are sent to that neighbor as unicast messages.
EIGRP ID
Choose the Autonomous System (AS) number of the EIGRP routing process.
Neighbor
Type the IP address of the neighbor.
Interface
Choose the interface through which the neighbor is available.
Summary Address
—Define summary addresses in either of these scenarios:
•
If you want to create summary addresses that do not occur at a network number boundary
•
If you want to use summary addresses on a router with automatic route summarization disabled.
If any more specific routes are in the routing table, EIGRP advertises the summary address out the interface with a metric equal to the minimum of all more specific routes.
EIGRP ID
Choose the Autonomous System (AS) number of the EIGRP routing process.
Network Address
Type the IP address of the summary address.
Net Mask
Choose the network mask of the summary address.
Administrative Distance
Type the distance value of the summary address.
Default: 5
Table 50 - EIGRP Fields (Continued)
Field
Description
IMPORTANT
Setting metrics is complex and is not recommended without guidance from
an experienced network designer.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......