To run multi-mode Express Setup in Medium Press mode, follow these steps.
1.
Apply power to the switch.
When the switch powers on, it begins its power-on sequence. The
power-on sequence can take as many as 90 seconds to complete.
2.
Make sure that the power-on sequence has completed by verifying that
the EIP Mod and Setup status indicators are flashing green:
•
If the switch fails the sequence, the EIP Mod status indicator turns
red.
•
If you do not press the Express Setup button within 5 minutes after
the sequence completes, the Setup status indicator turns off.
3.
Press and hold the Express Setup button until the Setup status indictor
flashes red during seconds 6…10, and then release.
The following occurs:
•
The Setup status indicator flashes green during seconds 1…5, and
then red during seconds 6…10.
•
The switch broadcasts a DHCP request out of all ports on VLAN 1.
•
VLAN 1 is configured with the IP address returned by the DHCP
server.
•
The default login credentials are set to the following:
–
User name: [no user name/blank]
–
Password:
switch
•
CIP is enabled on VLAN 1 with CIP Security password set to
switch
.
4.
Configure network settings:
•
To complete the configuration via Device Manager, see
•
To complete the configuration via the Logix Designer application,
see
Run Multi-mode Express Setup in Long Press Mode
Press and hold the Express Setup button until the Setup status indicator flashes
alternating green and red during seconds 16…20, and then release.
Upon release of the Express Setup button, the switch restarts with factory
default settings.
IMPORTANT
You must complete the switch setup within 10 minutes of releasing
the Express Setup button. Otherwise, the switch exits Express Setup.
IMPORTANT
Long Press mode overwrites all existing configuration files in internal or
external memory and resets the switch to use factory default settings.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......