Technical Data
90/ 122
Powerlift prefabricated pumping station
6.2 Submersible pumps – non-faecal wastewater
6.2.1 SAT-100/D, SAT-150/D and SAT-200/D
Characteristic data and use limits
Key data
SAT
100/D
150/D
200/D
Type of cable for connection cable:
4G1
4G1
4G1
Pump motor operating voltage [V]:
400
400
400
Frequency [Hz]:
50
50
50
Pump motor speed [1/min.]:
2,700
2,665
2,740
Pump motor power input P1 [kW]:
1.3
1.6
2.0
Pump motor output P2 [kW]:
0.9
1.1
1.5
Pump motor nominal current [A]:
2.3
2.7
3.6
Maximum starts per hour:
30
30
30
Maximum ball through-flow [mm]:
15
15
15
Medium temperature range [°C]:
40
40
40
Fluid pH-value:
6 – 14
6 – 14
6 – 14
Fluid viscosity [mm²/s]:
1.005
1.005
1.005
Medium density [kg/ m³]:
1,100
1,100
1,100
Weight [kg]:
19.5
20.5
21.5