Commissioning
62/ 122
Powerlift prefabricated pumping station
Function of the controls
Description
Function
Explanation
Display
Selection of the
menu items
The rotary knob can be used to select the menu items in the display
panel.
The display automatically changes back to the basic setting after 20
seconds.
Selection
Acknowledge
Acknowledge
malfunction
The button is used to acknowledge malfunction signals and messages
after removing the cause of the fault.
If the malfunction is not corrected, only the group fault alarm relay and
the alarm sound signal (e.g. flood alarm) are switched off.
Confirm setting
The button is used to save the settings made in the menu items.
MANUAL
Switch on manual
operation
The buttons for Pump P1 and P2 are used to switch on the pumps
independently of the “level switching”.
Manual operation is switched off automatically after 2 minutes.
0
Switch off operation
The buttons for Pump P1 and P2 are used to switch off automatic mode
or manual operation of the pumps.
AUTO
Switch on
automatic mode
The buttons for Pump P1 and P2 are used to switch on automatic
operation of the pumps and to control them automatically via the “level
switching”.
Explanation of the display elements
Description
Meaning
Explanation
Flood
alarm
Flood alarm group
fault
Fault signal: The water level in the tank has reached the “Flood alarm”
level
Malfunction
Pump P1 or P2
malfunction
Malfunction
Pump(s) not in operation
Operation
after-running
Operating display
for Pump P1 or P2
LED illuminates: Pump(s) in operation
LED flashes: Pump(s) in operation via the after-running function
Automatic
Pump P1 or P2
operation mode
LED illuminates: Automatic mode
LED flashes irregularly: Manual mode
LED flashes irregularly: Manual operation was switched off automatically
after approx. 2 minutes