Commissioning
76/ 122
Powerlift prefabricated pumping station
Menu
point
Unit
Pump type
Settings with level sensor:
A
+
B
C
D
E
AL
PL
BL
OFF
AL
PL
BL
OFF
AL
*
PL
*
BL
*
OFF
*
20 mA =>
level
cm
–
–
–
400
Language
–
German
*
Previously set under “level control” menu item = Set
4-20mA Interface
“and under”
20 mA => Level =
400
.
**
Value = 0 with version with air bubble injection. With version without air bubble injection, value assessment
during trial run: Water level must remain approx. 5 cm under lower edge of back pressure hole.
***
With Level Control PS 2 Control System: Setting via separate motor protection switch.
4.3.7 Powerlift PSD-B-2200 with T
Basin
= 505
Menu
point
Unit
Pump type
Settings with level sensor:
A
+
B
C
D
E
AL
PL
BL
OFF
AL
PL
BL
OFF
AL
*
PL
*
BL
*
OFF
*
Flood AL
=
AL
Peak load
ON =
SL
Base load
ON =
BL
Base load
OFF =
OFF
cm
SAT-Q 300/65/D
119 109 99 11 150 140 130 31
–
119 109 99 11
SAT-Q 300/80/D
119 109 99 11 150 140 130 31
119 109 99 11
SAT-Q 400/65/D
112 102 92 11 150 140 130 38
112 102 92 11
SAT-Q 400/80/D
112 102 92 11 150 140 130 38
112 102 92 11
SAT-Q 550/80/4/D
111 101 91 11 150 140 130 39
111 101 91 11
SAT-Q 750/80/D
110 100 90 11 150 140 130 40
110 100 90 11
SAT-Q 1000/100/D
106 96 86 11 150 140 130 44
106 96 86 11
SAT-Q 1000/100/4/D
106 96 86 11 150 140 130 44
106 96 86 11
SAT-Q 1500/100/D
106 96 86 11 150 140 130 44
106 96 86 11
SAT-Q 300/80/4/D
111 101 91 11 150 140 130 39
111 101 91 11
KL-AT-M 200/4/80/D-Ex 116 106 96 11 150 140 130 34
116 106 96 11
KL-AT-M 300/4/80/D-Ex 111 101 91 11 150 140 130 39
111 101 91 11
KL-AT-M 400/4/80/D-Ex 111 101 91 11 150 140 130 39
111 101 91 11
KL-AT-V 400/2/80/D-Ex 109 99 89 11 150 140 130 41
109 99 89 11
KL-AT-V 400/4/100/D-
Ex
107 97 87 11 150 140 130 43
107 97 87 11
KL-AT-V 550/2/80/D-Ex 109 99 89 11 150 140 130 41
109 99 89 11